  • Wide range of GZ1: thermal magnetic
  • Easier to install and operate with standard screws


GZ1E are 3 pole (3P) thermal-magnetic circuit breakers for motor protection, conforming to standards IEC 60947-2 and IEC 60947-4-1, with a thermal setting range 6...10A. It provides IP41 in GV2MC01 enclosure and IP55 in GV2MC02 enclosure. It procures standard reliability and 0.1M cycles electrical/mechanical durability. These circuit breakers are designed for connection by screw clamp terminals. Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

RangeEasy TeSys
Range of productEasy TeSys Power
Product or component typeCircuit breaker
Device short nameGZ1E
Device applicationMotor
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-1 appendix 7.1.6
ColourGrey (RAL 7011)
Poles description3P
Network typeAC
Utilisation categoryAC-3
Network frequency50/60 Hz conforming to IEC 60947-2
Mounting modeBy clips
By screws
Mounting supportRail
Mounting positionAny position
Motor power kW2.2 kW at 230 V AC 50/60 Hz
4 kW at 400 V AC 50/60 Hz
4 kW at 440 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
7.5 kW at 690 V AC 50/60 Hz
Breaking capacityIcu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control typePush-button
Thermal protection adjustment range6…10 A
Magnetic tripping current138 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Power dissipation2.5 W (per pole)
Mechanical durability100000 cycles
Electrical durability100000 cycles for AC-3
Maximum operating rate25 cyc/h
Connections - terminalsScrew clamp terminals 2 1…6 mm² - cable stiffness: solid
Screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end
Screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end
Height89 mm
Width44.5 mm
Depth78 mm
Product weight0.26 kg
StandardsIEC 60947-2
IEC 60947-4
Product certificationsCCC
CE
CB
Protective treatmentTH
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…60 °C
Ambient air temperature for storage-40…80 °C
Fire resistance960 °C conforming to IEC 60695-2-1
Operating altitude2000 m
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height4.800 cm
Package 1 Width8.400 cm
Package 1 Length9.000 cm
Package 1 Weight256.000 g
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight6.507 kg
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Height75.000 cm
Package 3 Width60.000 cm
Package 3 Length80.000 cm
Package 3 Weight112.615 kg

 

 


 

You may also like

Shopping Bag

Cart Is Empty